CHAPTER 2 - SPECIFICATIONS
About Chapter 2
PLUS
HI 2160RC
Specifications
Input
Output
Storage
Instrument
Resolution
Remote Control
Options
Alarms (Relays)
Analog to Digital
Specifications
Chapter 2 lists the specifications for the HI 2160RC
Specifications are listed for the standard instrument and for instruments
fitted with optional equipment. The specifications listed are designed to
assist in the installation, operation and troubleshooting of the instru-
ment. All service personnel should be familiar with this section before
attempting an installation or repair of the instrument
Up to 4 (four) 350 ohm load cells (10 volt excitation)
Full Wheatstone Bridge, Strain Gauge Load Cells
Control Out - Isolated Outputs, user selectable
4-20 Milliamp
0-20 Milliamp
0-5 Volt DC
0-10 Volt DC
Battery Backed RAM
Secure Memory Module Calibration Data
Display: 1:985,000 (for 3 mv/v)
Internal: 1:1,048,576
Allen Bradley Programmable Logic Controller (PLC)
Profibus (Various PLCs)
Serial Port - RS-232C (Standard)
Serial Port - RS 422/485
Remote Set Point (Analog)
Rate Tolerance Alarms
Refill Alarms
Rate Exception Control Alarm (REC)
Shut Off
ON/OFF
Conversion Rate: 20 updates per second
Averages: 1 to 200 selectable in increments of 1
Rate of Change Time Base: 1, 2, 3, 4, 5, 6, 8, 10, 12, 15, 20, 30, 40,
50, 60, 100, 120 (seconds)
Non-Linearity: 0.0015% of Full Scale
Common Mode Rejection: 100 dB at or below 60Hz
Common Mode Voltage: 300 VAC or VDC maximum (with respect
to earth ground)
Chapter 2 - Specifications
PLUS
rate controller.
2-1