PLUS
HI 2160RC
MANUAL
Down Loading Rate
Set Points Via
Analog Signal for
PLC's that are not
Equipped with
PROFIBUS or Allen
Bradley Remote I/O
8-26
Step 1. Set the LO Output Signal (4 milliamps) to 0.00. Now 4
milliamps = 0 lbs/hr. (See Remote Set Points Option for
Ratio Control Applications, Setting The LO Output Signal
Parameter above)
Step 2. Set the HI Output Signal (20 milliamps) to 200.0 lbs/hr.
(See Remote Set Points Option for Ratio Control Applica-
tions, Setting the HI Output Signal Parameter above)
Step 3. Set the Percentage at 10%. (See Remote Set Points Option
for Ratio Control Applications, Setting a Percentage of
the HI Output Signal above)
•
Equipment Required for the PLC
•
Analog Output Module
•
Relay Module
•
Equipment Required for the HI 2160RC
•
Remote Set Point Option Card that matches the Analog Output
Signal of the PLC.
0-20 Milliamps
4-20 Milliamps
0-5 Volts
0-10 Volts
Step 1. Set the jumpers for the amperage or voltage range that
matches the analog signal of the analog output module in
the PLC. (See Chapter 3 for Instructions)
Step 2. Set the Current Sense jumper for single controller, or mul-
tiple controllers. (See Chapter 4 Current Sense Selection
Table)
Step 3. Typical system incorporating a PLC and three (3) HI
PLUS
2160RC
ity. (See Fig. 8-27 and 8-28)
PLUS
rate controllers with remote set point capabil-