Components - Toshiba TOSDIC-CIE DS Installation And Wiring Manual

Hide thumbs Also See for TOSDIC-CIE DS:
Table of Contents

Advertisement

Components

Table 2.3 lists the items used for the TOSDIC-CIE DC system Ethernet control LAN.
Table 2.3 List of TOSDIC-CIE DC System Ethernet Control LAN Items
Name
AUI cable
B system AUI cable
10BASE5 coaxial cable
10BASE-T twisted pair
cable
B system 10BASE-T
twisted pair cable
Connector for 10BASE5
coaxial cable
Terminator
Grounding terminal
Optical fiber cord
is the cord length.
Optical fiber cable
Transceiver
Multi-port transceiver
Hub
Optical repeater
Electric repeater
Optical transceiver
(Note) For cables, refer to Appendix 3. Each B system cable has a tape attached to it so that it is identified as B system. However, its
function and performance are same as that of the ordinary cables. No connector is attached to a 10BASE5 coaxial cable to
adapt any wiring in the field. Install the connector for 10BASE5 coaxial cable.
Type (Figure Number)
ZCA102A***1
ZCA112A***1
ZCA108A***1
ZCA101A***1
ZCA111A***1
EA06NPC
DL-NP-50OHM
EA11GND
TK-G3004S+KFC1P-
S
TK-G3004S+KFC1P-
S
CT-G3004S-05-NME
HLT-211TZ-WNTP
MTX-210TZ-NTP
MPR-855T
MPR-410/T
MPR-410/T-E
HLT-320Z
Cable used indoor and in cabinets
Has D-sub15 connectors (mould type) at both ends.
Cable used indoor and in cabinets
Has D-sub15 connectors (mould type) at both ends.
Used as B-system cable in redundant configuration.
Cable for the control room and field.
Used for indoor wiring outside the cabinet.
Category 5 twisted pair cable without shield (UTP5 cable).
Has RJ-45 connectors at both ends. Connects a hub and OIS-DS51
or SVR-DS51 in the operator room.
Category 5 twisted pair cable without shield (UTP5 cable).
Has RJ-45 connectors at both ends. Connects a hub and OIS-DS51
or SVR-DS51 in the operator room. Used as B-system cable in
redundant configuration.
Attached to both ends of a 10BASE5 coaxial cable.
Connector shape : N-type.
Attached to the transceiver at the network termination.
Impedance: 50?, Connector shape : N-type.
Used to ground the shield of the 10BASE5 coaxial cable segment.
Cord to connect the optical repeater and splice box.
Optical fiber cord with a connector at one end.
Cord to connect optical repeaters indoors or in the cabinet.
Optical fiber cord with connectors at two ends.
Cable that connects splice boxes.
5-wire optical fiber cable, non-metallic type (one wire is a spare.)
Device that connects a 10BASE5 coaxial cable and AUI cable.
Device that connects a 10BASE5 coaxial cable and AUI cable. Has 2
channels of AUI port. Used in the redundant configuration of PCS-
DS main unit.
Device that connects a 10BASE5 segment and 10BASE-T segment.
AUI port × 1, 10BASE-T port × 8.
Device that connects a 10BASE5 segment or 10BASE2 segment to
optical fiber segment (complied to FOIRL).
Optical connector (FC-type) × 1, AUI port × 1, BNC port × 1.
Device that connects a 10BASE5 segment to 10BASE5 segment,
10BASE2 segment to 10BASE2 segment, or 10BASE5 segment to
10BASE2 segment.
AUI port × 2, BNC port × 2.
Device that connects AUI to optical fiber segment (complied to
FOIRL). Optical connector shape: FC-type.
2. Wiring of PCS-DS51
Usage
31

Advertisement

Table of Contents