Regin CORRIGO L10 Manual
Hide thumbs Also See for CORRIGO L10:

Advertisement

Manual C
L10
2002-11
ORRIGO
C
L10 is a new controller which has been designed to be easy to use and
OORIGO
operate. It has been designed for use in less complex air-handling systems. The
controller has a display and built in indicator on the front for alarm and is operated
by means of clearly defined buttons.
The controller has been designed for mounting on a DIN rail, in norm housing or on
the front of a cabinet.
The required functions are selected with the help of questions in normal script or by
means of a code under the configuration menu depending on the type of application.
The controller has a year-base clock and automatic summer/winter time changeover.
The menu system works with different user-levels to show settings and to allow
settings to be altered. This means that non-technical staff can feel secure while
using the system since it is impossible, on the lower user-levels, to programme
incorrect settings when checking operating status, parameter values, alarms etc.
During normal operation, without pressing any buttons, the display also shows the
most important operating statuses such as setpoint/current value, sequence-output
control and time/date/version etc.
We hope you will be satisfied with your C
simpler and more economic running of your control systems.
C
L10 for use with air handling systems comes with or without LON
ORRIGO
communication option.
L10
Temperature controller for up to three sequences
L10-LON Same as L10 bus also has LON Works communication.
Page 4
5
6
10
14
22
24
25
27
28
30
31
Introduction
and that it will provide you with
ORRIGO
Models
Contents
Technical data
Overview of in- and outputs
Installation and wiring
Handling and menu system
Configuration of functions
Description of inputs/outputs
Scheduler
Settings
Overview of alarm functions
Commissioning protocol
Configuration guide
Index
3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CORRIGO L10 and is the answer not in the manual?

Questions and answers

Summary of Contents for Regin CORRIGO L10

  • Page 1 Introduction L10 is a new controller which has been designed to be easy to use and OORIGO operate. It has been designed for use in less complex air-handling systems. The controller has a display and built in indicator on the front for alarm and is operated by means of clearly defined buttons.
  • Page 2: Technical Data

    Technical data Supply voltage 24 V AC +/- 15% Power consumption 3 VA Ambient temperature 0...50°C Storage temperature -40...+50°C Ambient humidity Max 90%RH Size (l x h x d) 105 x 110 (incl terminals) x 59 mm Protection class IP20, panel mount IP40 Mounting On DIN-rail in cabinet On panel front with assembly kit FMC or FMK...
  • Page 3 - L10 ORRIGO Overview 4 analogue sensor inputs for Pt1000 type sensor 4 digital inputs 3 analogue outputs 0...10 V 5 digital outputs L10 has temperature control with up to 3 sequences, optional DX cooling Analogue outputs - 0...10 V Analogue inputs - temperature AO1 Y1 - Heat or cooling Outdoor temp.
  • Page 4 Installation Corrigo L10 can be mounted on a DIN-rail in a panel or in a panel front. Panel front assembly kit (See page 2) When C L10 is mounted in a panel front the procedure is made easier by ORRIGO using the assembly kit FMC.
  • Page 5 Wiring diagram L10 Net A (L10-LON only) Net B (L10-LON only) DI4 Alarms cooler/Exchg./Smoke/Ext. DI3 Ext.runtime/Smokealarm/Ext. alarm DI2 Pump monitor DI1 Fan malfuct.alarm/Fan indicator DI+ Common DI1..DI4 C1/2 24V AC Common DO1 and DO2 24V AC DO2 DX cool stage 2 / Fan interl. 24V AC / 0.5A DO1 DX cool stage 1 DO3..5...
  • Page 6 Wiring AI Analogue inputs L10 has 4 analogue inputs, AI1...AI4. ORRIGO These inputs are for use with temperature sensors of type Pt1000. Exception: The AI4 input is used as a digital input when the unit is configured with overheat protection on an electric heater. In that case, connect this input to a poten- tial free closing contact.
  • Page 7 Wiring Analogue outputs AO L10 has 3 analogue outputs, AO1...AO3. ORRIGO Outpul levels are 0...10 V DC, 5 mA. Short circuit protected. Reference point is terminal 23, signal neutral which is internally connected to terminal 25, system neutral. The outputs AO1...AO3 make up the temperature controlling sequence. Function for each output is determined by configuration setting but the order is always Y3 ? Y2 ? Y1 on increasing heat demand.
  • Page 8 Operating buttons Up arrow - scrolls upwards in menu selections. In “Edit-mode“ this key is used to INCREASE the selected value. If the key is held in depressed position it will repeat. Down arrow - scrolls downwards in menu selections. In “Edit-mode“ this key is used to DECREASE the selected value.
  • Page 9: Scheduler

    Information series - scrolling display Setpoint/Actual * CORRIGO L10 * Y1 / Y2 / Y3 20,0°C / 20,0°C TU 14:10 AUT:ON 0% / 45% / During normal running when the buttons are not in use a series of menu pages is shown.The display alternates between a general display with product description and...
  • Page 10: Settings

    Menu information If the user attempts to make changes that cannot be made or which lie outside his user level the controller will display the following information: Unauthorized No changes in Make new logon this menu Alarms When alarms are activated they are displayed in the alarm queue and also as a flashing red light on the display panel on the front of the controller in the event of an alarm.
  • Page 11 3. Should the code for level three be lost the sys- Important! tem can only be opened by means of a code number which can be obtained from REGIN. This code number is time limited. Manual C 2002-11...
  • Page 12: Table Of Contents

    Automatic restart after changing When one or more parameters have been changed the controller will restart when the user leaves the configuration menu. CONFIGURATION-Corrigo L10 A B C D . E F G H . I J K Config Code A Control function 0.
  • Page 13: Supply Air Control

    Configuration Configuration settings CONTROL FUNCTION SEQUENCE Y1,Y2, Y3 HEATER TYPE FROST PROTECTION SHUT-DOWN MODE PUMPSTOP FUNCTION AI1 FUNCTION DI1 FUNCTION DI3 FUNCTION DI4 FUNCTION DO1/DO2 FACTORY SETTINGS. Used for resetting unit to factory settings (Not part of the configuration code). Control function.
  • Page 14: Room Control With Cascaded Supply Air

    Configuration Supply air control with outdoor temperature compensation Supply air control with outdoor temperature The temperature sensor Supply Air (AI3) controls the sequences to reach setpoint. compensation. The setpoint is compensated with respect to the temperature at outdoor temperature sensor (AI1). Parameters are set in the menu ”Settings” where menus for outdoor compensation will become accessible when this selection is made.
  • Page 15: Room Control With No Supply Air Sensor

    Configuration Room temperature control with minimum-maximum limitation of supply air Room control with temperature min/max limiting of supply air The temperature sensor Room (AI2) controls the sequences so that the setpoint is temperature. reached. The temperature at the Supply air sensor (AI3) is kept within the minimum and maximum limits set.
  • Page 16: Heat

    Configuration Output Output sequence Y1, Y2, Y3 level The function of the outputs can be set individually. The sequence or- der, however, is always the same: Temperature At increasing heat requirement Y3 is always activated first, then Y2 and finally Y1. Setpoint B.
  • Page 17: Y1 Automatic Reset

    Configuration Controlling plate heat exchanger Plate heat exchanger means that the output controls e.g. a damper actuator to vary the capacity of the heat exchanger. Defrosting plate heat exchanger Ice-build up sensor (pressure switch) is connected to DI4. On ice build-up the defrosting function is activated.
  • Page 18: G Function For Ai1

    DI1 has to be closed. When the fan control output (DO3) is activated, Corrigo L10 awaits a status running signal at DI1. If no status running signal is present at DI1 after a preset delay time, a fan alarm is activated and the system stops.
  • Page 19: K Function For Do1, Do2

    Factory settings Basic setting Use this option to return Corrigo L10 to factory setting. Press the ? key, choose ”Yes” and confirm choice with the OK key. If you enter the ? -mode and change your mind, you can leave the edit mode by pressing the Esc key and nothing will be changed.
  • Page 20 Inputs This menu is used to inspect current values/states for the AI and DI inputs. Outdoor temperature or external setpoint Room temperature Supply air temperature Frost protection sensor When frostprotection is selected with water heater or Overheat protection When electric heater is used DI1 Fan malfunction or fan status indicator.
  • Page 21 Outputs Shows present values for AO1...AO3 and DO1...DO5. Outputs can be set manually. This requires user level 1. If output is not set back to AUTO-mode within 15 seconds, an ”Output in manual” alarm is activated. AO1 Y1 - Heat or Cooling AO2 Y2 - Damper, plate exchanger, rotating exchanger or cooling AO3 Y3 - Cooling DO1 Control DX-Cooling stage 1...
  • Page 22 Scheduler L10 has a scheduler based on a one-week period. This means that the days ORRIGO of the week can be individually selected or deselected in the period. The scheduler can handle power losses for at least 24 hours without loss of data. Clock Clock.
  • Page 23 Settings All parameter settings have been gathered under this menu. Explanation of control Which parameters are shown or hidden depends on which control function has been funktions selected. 0. Supply air control 1. Supply air control with 1. Running mode outdoortemp.
  • Page 24 Settings - continued 13.Outdoor compensation, breakpoint 1. Control function 1, 5. 14.Outdoor compensation, breakpoint 1. Control function 1, 5. 15.Outdoor compensation, breakpoint 1. Control function 1, 5. 16.Outdoor compensation, breakpoint 1. Control function 1, 5. Outdoor compensation Values for compensation can be freely set but the breakpoints should be ordered with the highest (highest outdoor temp) at 4 and lowest (lowest outdoor temp) at 1.
  • Page 25 30.Blocking conditions for alarm output The alarm output can be blocked during certain times of day/week so that alarms are not forwarded during these periods (for example: night time and weekends). Important alarms however, such as frostprotection, overheat protection and smoke alarms always activates the alarm output and will not be affected by this setting.
  • Page 26: Commissioning Protocol

    Commissioning protocol Site System Date Commissioned by: Pg 1 No value written means default value Configuration Default setting Actual setting Config code 0501.0000.000 ____._____._____ A. CONTROL FUNC. 0 Supply air ctrl _______________ B. SEQUENCE Y1/Y2/Y3 5 Heat/P-exchg./Cool _______________ C. HEATER TYPE 0 Water heater _______________ D.
  • Page 27 Commissioning protocol Site System Pg 2 Date Commissioned by No value written means default value Scheduler Default setting Actual setting Period 1 MTWTF 08:00-17:00 _______________ Period 2 _______________ Period 3 _______________ more settings 1 Setpoint frost guard 7°C _______________ 2 Setpoint shut-down mode 25°C _______________ 3 Pumpstop.
  • Page 28 CONFIGURATION - Corrigo L10 A B C D . E F G H . I J K Configuration code A Control function 0. Supply air control 1. Supply air control with outdoor temperature compensation 2. Room control with cascaded supply air temperature control 3.
  • Page 29: Index