[ VII Control ]
Priority order of the operation signal sources
Unit operation (Run/Stop) *5
Operation mode
Capacity change mode
(The contact ON has priority.)
Fan mode
(The contact ON has priority.)
*1 When the Anti freeze contact is ON during heating operation, the setting change is ineffective.
*2 Changing by contact is effective during heating operation.
*3 Capacity change mode cannot be set from AE-200.
*4 Fan mode cannot be set from PAR-W21MAA.
*5 The ON/OFF contact and Cooling/Heating contact setting can only be changed when the power is turned on.
HWE1417B
No-voltage contact
Cooling *1*5
Heating *1*5
Heating ECO *1*2
Anti freeze *2
Remote controller
PAR-W21MAA or
PAR-W31MAA
The last setting has priority.
The last setting has priority.
The last setting has priority.
The last setting has priority.
The last setting has priority.
OFF
ON
OFF
ON
- 84 -
Input from centralized
controller AE-200 or BMS
Effective *3
-
Ineffective
The last setting has priority. *4
Ineffective