[ VII Control ]

[2] Operating characteristics and Control Capabilities

Outline of Control Method
-1- Operating characteristics
Function
Unit
Pressure
protection
switch
Pressure
sensor
Compressor overcurrent relay
Fan overcurrent protection
Thermis-
tor
Pump
Water temperature thermister
control
Freeze-up protection circuit
HWE1417B
Component
Symbol
High-pressure
63H
switch
High-pressure
HP
sensor
Low-pressure
LP
sensor
Discharge refrig-
TH11
erant temp.
TH21
(Discharge temp.
overrise protec-
tion)
Outlet water
TH3
Air-side HEX re-
TH6
frigerant temp.
TH26
Water-side HEX
TH7
refrigerant temp.
TH27
ACC inlet refriger-
TH5
ant temp.
TH25
Inverter heatsink
THHS
temp.
TH1-3
Control/
Ac-
Unit
Detection
tion
HP
ON
MPa
OFF MPa
HP
OFF MPa
LP
OFF MPa
Compressor
OFF
A
current
Fan current
Limit
A
Discharge
OFF
ºC
gas temp.
Outlet water
OFF
ºC
temp.
(cooling)
Outlet water
OFF
ºC
temp.
(heating)
SC
-
ºC
(cooling)
SC
-
ºC
(heating)
SH
OFF
ºC
INV. heat-
OFF
ºC
sink temp.
Water temp.
ON
ºC
OFF
ºC
- 96 -
Trigger condition
(3.25)
4.15
3.9
The low pressure has dropped below 0.1 MPa.
During water cooling, the low pressure has
dropped below 0.56 MPa.
During brine cooling, the low pressure has
dropped below 0.25 MPa.
33
1.9
If a discharge gas temperature of 120ºC or above
was detected three times in 1 hour, the unit will
make an abnormal stop.
An outlet water temperature of 3ºC was detected.
An outlet brine temperature of -15ºC was detected.
An outlet water temperature of -65ºC was detected.
-
-
ACC inlet SH above 20ºC has been detected for 10
minutes.
A temperature above 95ºC has been detected for
10 minutes.
3
5
The pump turns on when the water temperature
has reached below the "ON" threshold when the
compressor is stopped.
GB