[ II Restrictions ]

[7] Water Pipe Installation

1. Schematic Piping Diagram and Piping System Components
<1> Water circuit
Please build the water circuit so that it is a closed
system.
Do not use water directly for showers or other applications.
Do not allow other heat source water to mix with the water
circuit.
Build a water circuit as inlet water temperature fluctuation is
within 5ºC/10 minutes.
Indicates the direction of
the flow.
Unit
Water
side heat
exchanger
1
Union joints/flange joints
Thermometer
2
Water pressure gauge
3
V
l a
e v
4
Flexible joint
5
Pump
6
Air vent valve
7
Expansion tank
8
W
t a
r e
p
p i
e
9
D
a r
n i
v
a
v l
e
10
Strainer
11
12
Flow switch
Drain pipe
13
HWE1417B
Water supply
Required to allow for a replacement of equipment.
Required to check the performance and monitor the operation of the units.
Recommended for checking the operation status.
R
e
q
i u
e r
d
o t
a
o l l
w
f
r o
Recommended to prevent the noise and vibration from the pump from being transmitted.
Use a pump that is large enough to compensate for the total water pressure loss and
supply sufficient water to the unit.
Install air venting valves to the places where air can accumulate.
Automatic air vent valves (such as
Install an expansion tank to accommodate expanded water and to supply water.
U
s
e
p
p i
e
s
h t
t a
a
o l l
w
n I
t s
l l a
d
a r
n i
v
a
v l
e
s
s
o
Install a strainer near the unit to keep foreign materials from entering the water-side
head exchanger.
Required to protect the unit.
Install the drain pipe with a downward inclination of between 1/100 and 1/200. To
prevent drain water from freezing in winter, install the drain pipe as steep an angle as
practically possible and minimize the straight line.
For cold climate installation, take an appropriate measure (e.g., drain heater) to prevent
the drain water from freezing.
Condensation may form in the machine room, depending
on the operation status.
Securely attach the drain pipe.
Overflowed water
To drain outlet
Minimum upward
gradient of 1/200
a
e r
p
a l
c
e
m
e
t n
r o
c
e l
a
n
n i
g
f o
') are effective.
7
f
r o
e
a
y s
a
r i
p
u
g r
n i
, g
a
n
d
p
o r
h t
t a
w
t a
r e
c
a
n
b
e
d
a r
n i
e
d
- 27 -
Air conditioning
floor heating
etc
h t
e
f
o l
w
a
d
u j
s
e t
. r
v
d i
e
a
d
e
q
u
a
e t
n i
s
l u
t a
o i
. n
f
r o
s
e
v r
c i
n i
. g
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents