Mitsubishi Electric e Series Service Handbook page 92

Air-cooled chilling unit r410a
Hide thumbs Also See for e Series:
Table of Contents

Advertisement

[ VII Control ]
Priority order of the water-temperature-setting-input-signal sources
Water temperature can be controlled by using the signals from the four types of input sources (Heating, Heating ECO, Cooling,
Analog heating). The setting for the item with higher priority will override the settings for the items with lower priorities. The
water temperature will be controlled according to the temperature setting in the "Target water temperature" column that cor-
responds to a specific combination of the settings for the four items.
No-voltage contact input K04-K05 ON: Heating (EAHV-P900YA)
Priority 1
Priority 2
No-voltage
contact input
Analog input
K07-K08
or BMS
(SW 3-4:ON)
Anti freeze
ON
Ineffective
SW2-7: ON
OFF
SW2-7: OFF
*1 If SW2-5 is set to OFF, water temperature will be controlled by the built-in thermistor TH3 on the unit.
*2 This mode is disabled in EAHV-P900YA-H.
*3 EAHV-P900YA can also set Cooling.
*4 AE-200 and BMS cannot both be simultaneously connected. Only connect one or the other.
*5 The ON/OFF contact setting can only be changed when the power is turned on.
No-voltage contact input K04-K05 OFF: Cooling (EAHV-P900YA, EACV-P900YA)
* When the operation mode is Cooling, K07-K08 (Anti freeze) and K13-K15 (Mode change) are disabled.
Priority 1
Priority 2
Main board on
the unit
Analog input
Schedule
setting
SW2-7: ON
Ineffective
When schedule
has been set
SW2-7: OFF
When no
schedule has
been set
*1 If SW2-5 is set to OFF, water temperature will be controlled by the built-in thermistor TH3 on the unit.
*2 This mode is disabled in EACV-P900YA.
*3 EAHV-P900YA can also set Heating or Heating ECO.
*4 AE-200 and BMS cannot both be simultaneously connected. Only connect one or the other.
*5 The ON/OFF contact setting can only be changed when the power is turned on.
HWE1417B
Priority 3
Priority 4
No-voltage
Main board on
contact input
the unit
K13-K15
Schedule
Mode change
setting
Ineffective
Ineffective
Ineffective
Ineffective
When
schedule has
Ineffective
been set
ON
(Heating ECO)
When no
schedule has
OFF
been set
(Heating)
Priority 3
Remote controller
PAR-W21MAA or PAR-W31MAA
Input from centralized controller AE-200 or BMS (*4)
No remote
Manual
controller
setting
-
Ineffective
Ineffective
-
(Cooling)
When no RC is
-
used
-
Anti freeze (*2)
-
Heating ECO (*2)
-
Heating (*2)
-
Cooling
-
-
Priority 5
Remote controller
PAR-W21MAA or PAR-W31MAA
Input from centralized controller AE-200 or BMS
(*4)
No remote
Manual
controller
setting
-
Ineffective
-
Ineffective
-
Ineffective
-
Ineffective
When no RC is
-
used
-
Anti freeze
-
Heating ECO
-
Heating
-
Cooling (*2)
-
-
Schedule
setting
Ineffective
Ineffective
(Cooling)
-
-
-
-
-
When schedule
has been set (*3)
- 83 -
Target water
temperature
Schedule
setting
Ineffective
30ºC
Temperature
setting for the
Ineffective
analog signal
input
Heating or
Ineffective
Heating ECO
Ineffective
Heating ECO
-
Heating
-
30ºC
-
Heating ECO
-
Heating
-
Cooling
Target water
temp is
When
controlled
schedule has
according to the
been set (*3)
setting on the
remote
controller.
Sensor that becomes
Target water temperature
is set to ON) (*1)
Temperature setting for the
analog signal input
Cooling
Cooling
30ºC
Heating ECO
Heating
Cooling
Target water temp is
controlled according to the
setting on the remote
controller.
Sensor that
becomes
active
(when SW2-5
is set to ON)
(*1)
TH3
TH15
TH15
TH15
TH15
TH3
TH15
TH15
TH15
TH15
active
(when SW2-5
TH15
TH15
TH15
TH3
TH15
TH15
TH15
TH15
GB