Mitsubishi Electric e Series Service Handbook page 102

Air-cooled chilling unit r410a
Hide thumbs Also See for e Series:
Table of Contents

Advertisement

[ VII Control ]
• When the capacity control ratio input signal type is 2-10 V
• External analog input signal of 3 V: 0%
• External analog input signal of 9 V: 100%
• External analog input signal of between 3 and 9 V: the percent will be linearly interpolated.
Load ratio
*%: When the compressor frequency drops below 16 Hz, the compressor stops.
The frequency value that causes the compressor to stop varies depending on the outside temperature and water temperature.
HWE1417B
100%
*%
0%
2 V
3 V
9 V
10 V
Input voltage
- 93 -
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents