Mitsubishi Electric e Series Service Handbook page 79

Air-cooled chilling unit r410a
Hide thumbs Also See for e Series:
Table of Contents

Advertisement

[ V Electrical Wiring Diagram ]
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
*1. Definition of symbols in the "Error reset" column.
・・・ Errors that can be reset.
・・・ Errors that cannot be reset.
・・・ Errors that will be automatically reset after the cause of the error is removed.
*2. Power supply fault can be detected only when the switch setting "Automatic recovery after power supply fault " on the unit is set to
"Disable." (The default setting is "Enable.")
*3. If a unit comes to a stop due to a preliminary error, the unit will resume normal operation if the error conditions are cleared within a
certain amount of time. If the error conditions persist beyond the predetermined time, the unit will come to an abnormal stop.
*4. " * " shows types of components. (0/1: COMP for MAIN circuit, 2: COMP for SUB circuit, 5: FAN 1, 6: FAN 2, 7: FAN 3)
Display setting (Control board display *)
SW3-3: OFF
High pressure
Low pressure
* Display settings can be either of the MAIN BOX and the SUB box.
Display is switched in the 3 second intervals.
HWE1417B
FAN control (front view)
SUB CIRCUIT
Inside of the control box (front view)
C200
SUB BOX
52C2
R21
R22
DCL2
Control
Board 2
Noise
INV
Filter 2-1
Board 2
TB2
S
U
B
C
R I
C
U
T I
Error code
Error type
1102
Discharge temperature fault
1138
Hot water abnormal rise
1176
Discharge SH fault
1189
ACC inlet SH fault
1301
Low pressure fault
1302, 1303
High pressure fault
1503
Cold water abnormal drop
1510
Gas leak fault
1512
Low evaporation temperature fault
2500
Water supply cutoff (Flow switch)
2501, 2550
Water supply cutoff (Sensor)
4102
Open phase
4106
Power supply fault *2
4115
Power supply frequency fault
4116
Fan motor fault
4122
Fan interlock fault
4126
Analog input error
422*
Inverter bus voltage fault
423*
Inverter overheat protection fault
424*
Inverter overheat protection
425*
IPM error (inclusive)/overcurrent relay
426*
Control box Fan fault
5101
Water inlet temp 1 thermistor error (TH1)
5102
Water inlet temp 2 thermistor error (TH2)
5103
Water inlet temp 3 thermistor error (TH3)
5105
ACC inlet refrigerant temperature thermistor error (TH5/TH25)
5106
Air heat exchanger refrigerant thermistor error (TH6/TH26)
5107
Water heat exchanger refrigerant thermistor error (TH7/TH27)
5110
Outdoor temperature thermistor error (TH10)
5111
Discharge refrigerant temperature thermistor error (TH11/TH21)
5114
THHS sensor/Circuit fault
5115
External water sensor fault
5201
High pressure sensor fault
5202
Low pressure sensor fault
530*
ACCT sensor fault/Circuit fault
0403
Serial communication error
6500
Communication error between the MAIN and SUB units
6600
6602
6603
Communication error between the MAIN and SUB units
(Simple multiple units control)
6606
6607
6608
6831
Remote controller signal reception error 1
6832
Remote controller signal transmission error
6834
Remote controller signal reception error 2
6833
Remote controller over current
7113, 7117
Model setting error
SW3-3: ON
High pressure
Low pressure
Inlet water temperature
Outlet water temperature
Ambient temperature
DB2
FANCONT BOX
R13
52C1
C100
R11
MAIN BOX
R23
R12
DB1
DCL1
Noise
Noise
Noise
INV
Filter 1-2
Filter 2-2
Filter 1-1
Board 1
FANCONT
FANCONT
TB1
Board 2
Board 1
M
A
N I
C
Error reset *1
- 70 -
MAIN CIRCUIT
Control
Board 1
M-NET
Board
R I
C
U
T I
Preliminary error code *3
1202
none
1276
1289
1401
1402
none
none
1612
none
none
4152
none
none
4166
4172
none
432*
433*
434*
435*
436*
none
none
none
none
none
none
none
1211
1214
none
none
none
4301
431*
none
none
none
none
none
none
none
none
none
none
none
none