[ VII Control ]
• When the water temperature setting input signal type is 1-5 V
• External analog input signal of 1.5 V: Preset temp. A
• External analog input signal of 4.5 V: Preset temp. B
• External analog input signal of between 1.5 and 4.5 V: the preset temperature will be linearly interpolated.
Preset temp B
Preset temp A
• When the water temperature setting input signal type is 2-10 V
• External analog input signal of 3 V: Preset temp. A
• External analog input signal of 9 V: Preset temp. B
• External analog input signal of between 3 and 9 V: the preset temperature will be linearly interpolated.
Preset temp B
Preset temp A
HWE1417B
1 V
1 .5V
4.5 V
5 V
Input voltage
2 V
3 V
9 V
10 V
Input voltage
- 91 -