[ VII Control ]
Control Method
-9- Automatic operation of pump for freeze-up protection
1. Purpose
This is a function to protect the water circuit from freezing up in winter.
2. Pump wire connection
3. Natural freeze-up protection
Control method
Details
HWE1417B
CN510
7
6
5
4
3
2
1
K62
K61
TB6
Natural freeze-up protection based on the water temperature
Pump start conditions
Water temperature is within 3 ºC
Pump stop conditions
Water temperature is more than 5 ºC
M
MP
3
~
52P
52P
PL
Pump error
F
ELB
L1
L2
L3
- 101 -
power supply
3N~