[ VII Control ]
VII Control

[1] Functions and Factory Settings of the Dipswitches

1. Factory Switch Settings (Dip switch settings table)
SW
Function
1
2
3
4
5
Settings change or view
SW1
the settings
6
7
8
9
10
1
2
Model setting
3
4
Water-temperature
5
control option
6 Model setting
7 Analog input setting
SW2
Analog input signal
8
switching
Auto restart after power
9
failure
10 Model setting
1
Analog input type setting
2
3 Display setting *1
SW3
4 BMS setting *2
5 Model setting
6 Water/Brine setting *3
7
Model setting
8
9 Model setting
10 Model setting
"-" in the table indicates that the function in the corresponding row will be disabled regardless of the actual switch setting.
The factory setting for these items is OFF.
*1: LED display
High pressure
Pressure (MPa)
Low pressure
Pressure (MPa)
*2:Connection to a BMS requires an installation of Procon A1M (Modbus interface), which is available from MITSUBISHI ELECTRIC UK.
SW2-7
SW2-8
ON
ON
OFF
*3:Effective only on the EACV model
HWE1417B
Usage
These switches are used for setting
change with push switch SWP 1, 2 and 3.
Selects either the external water
temperature sensor or the built-in sensor
to be used to control water temperature.
Allows or disallows the analog signals
from a remote location.
Selects either the water temperature or
the capacity control ratio.
(Effective only when SW2-7 is set to ON.)
Enables or disables the automatic
restoration of operation after power failure
(in the same mode as the unit was in
before a power failure).
Selects analog input 4-20mA/
0-10V/1-5V/2-10V.
(Effective only when SW2-7 is set to ON
and SW3-4 is set to OFF.)
Switches the LED display of the control
board.
(Display is switched in the 3 second
intervals.)
Inlet water temperature
temperature (ºC)
Outlet water temperature
temperature (ºC)
SW3-4
OFF
ON
ON
ON
OFF
ON
Factory setting
MAIN
SUB
OFF setting
circuit
circuit
OFF
OFF
The 7-segment LED display is changed.
Depends
on the
-
Leave the setting as it is.
unit
Built-in sensor on the
OFF
-
unit
OFF
-
Leave the setting as it is.
Disallows the
OFF
-
external analog
signals.
OFF
-
Water temperature
An alarm will be
issued when power is
restored after a power
outage.
ON
-
The alarm will be
reset when the power
is turned off and then
turned back on.
OFF
OFF
Leave the setting as it is.
4-20mA : OFF OFF
OFF
-
1-5V
: ON
0-10V
: OFF ON
2-10V
: ON
High pressure
ON
ON
Low pressure
OFF
-
No input from BMS
OFF
-
Leave the setting as it is.
Water, Brine
OFF
OFF
(Outlet 5–25ºC)
OFF
-
Leave the setting as it is.
OFF
OFF
Leave the setting as it is.
OFF
-
Leave the setting as it is.
Ambient temperature
temperature (ºC)
Input from BMS
Target temperature
Capacity
Outdoor temperature
- 81 -
ON setting
External water
temperature sensor
(option)
Allows the external
analog signals.
Capacity control ratio Fixed OFF At a reset
Automatically
restores operation
after power failure.
1
/
2
OFF
ON
High pressure
Low pressure
Inlet water temperature
Outlet water temperature
Ambient temperature
Input from BMS
Brine
(Outlet -10–25ºC)
SUB
Setting
module
timing
Depends
Depends
on the
on the
setting
setting
Depends
on the
At a reset
unit
Required At a reset
Fixed OFF At a reset
Fixed OFF At a reset
Required Any time
Fixed OFF Any time
Fixed OFF Any time
Required Any time
Fixed OFF At a reset
Fixed OFF At a reset
Required At a reset
Fixed OFF At a reset
Fixed OFF Any time
Fixed OFF Any time