8 SYSTEM APPLICATION EXAMPLES

Safety monitoring function settings (robot controller)

8.2.9
Set the safety monitoring functions of the robot controller.
Function
Item
SLS1
XYZ monitoring speed
> Composite speed
SLS2
XYZ monitoring speed
> Composite speed
Speed limit override

Transmission interval monitoring time

8.2.10
Check the conditions of the transmission interval monitoring time (TM). The following shows calculation examples.
Item
Description
SCcpu
Safety cycle time of the safety CPU module
SCrc
Safety cycle time of the robot controller
LS
Communication cycle intervals
・ Transmission interval monitoring time of the safety programmable controller (TMact)
The transmission interval monitoring time set on the safety programmable controller must satisfy all of the
following conditions. Set a value equal to or higher than 16.3 [ms].
(1) TMact ≥ SCown × 3 = SCcpu × 3 = 3.00 × 3 = 9.00
(2) TMact ≥ SCoth × 2 + LS × 2 = SCrc × 2 + LS × 2 = 7.11 × 2 + 1.00 × 2 = 16.22
・ Transmission interval monitoring time of the robot controller (TMpas)
The transmission interval monitoring time set on the robot controller must satisfy all of the following conditions.
Set a value equal to or higher than 21.4 [ms].
(1) TMpas ≥ SCown × 3 = SCrc × 3 = 7.11 × 3 = 21.33
(2) TMpas ≥ SCoth × 2 + LS × 2 = SCcpu × 2 + LS×2 = 3.00 × 2 + 1.00 × 2 = 8.00
8-124 Application Example 2
Table 8-13 Safety monitoring function settings
Table 8-14 Parameters
Setting value
3500 [mm/s]
250 [mm/s]
5[%]
Value
Remarks
-
-
-
Remarks
3.00[ms]
Setting value
7.11[ms]
-
1.00[ms]
Setting value