Code 2
(cont.)
Coding in the delivered condition
56:0
Set DHW temperature
adjustable from 10 to
60 °C
58:0
Without auxiliary func-
tion for DHW heating
59:0
Cylinder heating
Start point: Set value
2.5 K
Shutdown point: Set
value +2.5 K
5A:0
No function
60:20
During DHW heating,
the boiler water tem-
perature is max. 20 K
higher than the set
DHW temperature
61:1
The circulation pump
starts immediately
62:10
Circulation pump with
max. 10 min run-on
Possible change
56:1
Set DHW temperature
adjustable from 10 to
95 °C
Note
Observe the max. per-
missible DHW tempera-
ture.
Change the control ther-
mostat "R" setting.
58:1
Input of a second set
to
DHW value, adjustable
58:95
from 1 to 95 °C (observe
coding address "56")
59:1
Starting point adjustable
to
from 1 to 10 K below the
59:10
set value
5A:1
Flow temperature de-
mand from the DHW cy-
linder is the maximum
system value
60:10
The difference between
to
the boiler water tempera-
60:50
ture and the set DHW
temperature is adjustable
from 10 to 50 K
61:0
The circulation pump will
be switched ON subject
to the boiler water tem-
perature
62:0
Circulation pump without
run-on
62:1
Max. run-on time adjusta-
to
ble from 1 to 15 min
62:15
Coding
89