Troubleshooting
Faults that are displayed at the programming unit
Fault codes
Fault code
System character-
on the dis-
istics
play
0F
Control mode
10
Regulates as if the
outside temperature
was 0 °C
18
Regulates as if the
outside temperature
was 0 °C
30
The burner is
started and stopped
via a thermostat
38
The burner is
started and stopped
via a thermostat
50
Cylinder primary
pump "ON":
Set DHW tempera-
ture = Set boiler
water temperature
Priority control is
cancelled or
With cylinder pri-
mary system:
Cylinder heating is
started and stopped
by cylinder tem-
perature sensor 2
51
With cylinder pri-
mary system:
Cylinder heating is
started and stopped
by cylinder tem-
perature sensor 1
58
Cause
Measures
Service
Service the equipment.
"0F" is only dis-
After the service, set
played in the fault
coding address "24:0".
history
Outside tempera-
Check the outside tem-
ture sensor
perature sensor (see
shorted out
page 111)
Outside tempera-
Check the outside tem-
ture sensor lead
perature sensor (see
broken
page 111)
Boiler water tem-
Check the boiler water
perature sensor
temperature sensor (see
shorted out
page 109)
Boiler water tem-
Check the boiler water
perature sensor
temperature sensor (see
lead broken
page 109)
Cylinder tempera-
Check the cylinder tem-
ture sensor 1
perature sensor (see
shorted out
page 109)
Cylinder tempera-
Check the cylinder tem-
ture sensor 2
perature sensor (see
shorted out
page 109)
(cont.)