Troubleshooting
Faults that are displayed at the programming unit
Fault code
System character-
on the dis-
istics
play
CE
Control mode
CF
Control mode
d1
Boiler cools down
d4
Boiler cools down
d6
Control mode
d7
Control mode
d8
Control mode
LON subscribers fault messages
Precondition:
The control unit must be programmed
as fault manager (code "79:1").
64
Cause
Measures
Communication
Check plug-in adaptor
fault
plug-in
(see page 119).
adaptor for exter-
Without plug-in adaptor:
nal safety equip-
Set code "94:0"
ment
LON communica-
Replace LON communi-
tion module fault
cation module (see
page 107).
Without module:
Set code "76:0"
Burner fault
Check the burner (see
page 30)
The high limit
Check the high limit
safety cut-out has
safety cut-out or the
responded or
burner, burner loop and
fuse F2 has blown
fuse/MCB F2
Fault at "DE1" in
Check connection to
plug-in adaptor
"DE1" (see page 120)
for external safety
equipment
Fault at "DE2" in
Check connection to
plug-in adaptor
"DE2" (see page 120)
for external safety
equipment
Fault at "DE3" in
Check connection to
plug-in adaptor
"DE3" (see page 120)
for external safety
equipment
(cont.)