Viessmann Vitotronic 200 Installation And Service Instructions Manual page 82

Table of Contents

Advertisement

Coding
Code 1
(cont.)
Coding in the delivered condition
03:0
Gas operation
Burner (modulating)
05:70
Burner curve
Burner
06:87
Maximum limit of the
boiler water tempera-
ture 87 °C
General
40:125
Motor runtime 125 s
77:1
LON subscriber number 77:1
DHW priority A1
A2:2
Cylinder priority for
heating circuit pump
Summer econ. A1
A5:5
With heating circuit
pump logic function
82
Possible change
03:1
Oil fired operation (irre-
versible)
03:2
This occurs automati-
cally, if an incorrect boiler
coding card is inserted or
none is present
05:0
Linear burner curve
05:1
Non-linear burner curve
to
(P
: P
T
max
05:99
P
in kW: Partial output at
T
of the servomotor run-
time
P
in kW: Maximum
max
output
06:20
Maximum limit adjustable
to
from 20 to 127 °C
06:127
40:5
Runtime adjustable from
to
5 to 199 s
40:199
LON subscriber number,
to
adjustable from 1 to 99
77:99
A2:0
Without cylinder priority
for heating circuit pump
A2:1
No function
A2:3
No function
to
A2:15
A5:0
Without heating circuit
pump logic function
A5:1
With heating circuit pump
to
logic function:
A5:15
Heating circuit pump
"OFF" (see table on
page 96)