Faults that are displayed at the programming unit
Fault code
System character-
on the dis-
istics
play
58
Cylinder primary
pump "ON":
Set DHW tempera-
ture = Set boiler
water temperature
Priority control is
cancelled or
With cylinder pri-
mary system:
Cylinder heating is
started and stopped
by cylinder tem-
perature sensor 2
59
With cylinder pri-
mary system:
Cylinder heating is
started and stopped
by cylinder tem-
perature sensor 1
60
Boiler with maxi-
mum temperature,
no output reduction;
mixer return tem-
perature control
"OPEN"
68
Boiler with maxi-
mum temperature,
no output reduction;
mixer return tem-
perature control
"OPEN"
70
Shunt pump con-
stantly "ON"
With cylinder pri-
mary system:
Mixer primary circuit
"Close"; no DHW
heating
Cause
Measures
Cylinder tempera-
Check the cylinder tem-
ture sensor 1 lead
perature sensor (see
broken
page 109)
Cylinder tempera-
Check the cylinder tem-
ture sensor 2 lead
perature sensor (see
broken
page 109)
Temperature sen-
Check temperature sen-
sor aJA shorted
sor (see page 110)
out
Temperature sen-
Check temperature sen-
sor aJA lead
sor (see page 110)
broken
Without temperature
sensor:
Set code "4A:0".
Temperature sen-
Check temperature sen-
sor aJB shorted
sor (see page 110)
out
Troubleshooting
(cont.)
59