Coding
Code 2
(cont.)
Coding in the delivered condition
14:...
Minimum burner run-
time in min
Delivered condition de-
faulted by the boiler
coding card
15:10
Runtime servomotor
mod. burner 10 s
16:...
Burner offset with start
optimisation in K (tem-
porary reduction of the
set boiler water tem-
perature after burner
start)
Delivered condition de-
faulted by the boiler
coding card
1A:...
Start optimisation in min
Delivered condition de-
faulted by the boiler
coding card
1b:60
Time from burner igni-
tion to the start of regu-
lation 60 s
1C:120
Never adjust
1F:0
With flue gas tempera-
ture sensor:
Flue gas temperature is
not monitored for burner
service indication
21:0
No hours run interval for
burner service
86
Possible change
14:0
Minimum runtime adjus-
to
table from 0 to 15 min
14:15
15:5
Runtime adjustable from
to
5 to 199 s
15:199
For Vitocrossal, see se-
parate service instruc-
tions,
for Vitocrossal 300, type
CV3, with MatriX burner
select "15:19".
16:0
Offset adjustable from 0
to
to 15 K
16:15
1A:0
Duration of start optimi-
to
sation adjustable from 0
1A:60
to 60 min
1b:0
Regulation delay adjusta-
to
ble from 1 to 199 s
1b:199
1F:1
"Service" will be dis-
to
played when the flue gas
1F:50
temperature limit (from
10 to 500 ºC) has been
exceeded;
1 step
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10000 h;
1 step
10 °C
100 h