Commissioning
Integrating a control unit into the LON
Boiler control unit
Subscriber no. 1
Code "77:1"
Control unit is fault
manager
Code "79:1"
Control unit trans-
mits the time
Code "7b:1"
Control unit trans-
mits outside tem-
perature
Set code "97:2"
Viessmann system
number
Code "98:1"
LON subscriber fault
monitoring
Code "9C:20"
Updating LON subscriber list
Precondition:
All subscribers must be connected
The control unit must be pro-
grammed as fault manager (code
"79:1")
Press the following keys:
1. L + d simultaneously for
approx. 2 s.
The subscriber check
has been initiated.
48
Vitotronic 200-H
Vitotronic 200-H
Subscriber no. 10
Subscriber no. 11
Code "77:10"
Set code "77:11"
Control unit is not
Control unit is not
fault manager
fault manager
Code "79:0"
Code "79:0"
The control unit re-
The control unit re-
ceives the time
ceives the time
Set code "81:3"
Set code "81:3"
The control unit re-
The control unit re-
ceives the outside
ceives the outside
temperature
temperature
Set code "97:1"
Set code "97:1"
Viessmann system
Viessmann system
number
number
Code "98:1"
Code "98:1"
LON subscriber
LON subscriber
fault monitoring
fault monitoring
Code "9C:20"
Code "9C:20"
2. e
(cont.)
Vitocom
Subscriber
no. 99
Device is fault
manager
Device re-
ceives the
time
The subscriber list is
updated after approx.
2 min.
The subscriber check is
completed.