Troubleshooting
Faults that are displayed at the programming unit
Fault code
System character-
on the dis-
istics
play
AC
Control mode
b0
Control mode
b1
Control mode
b4
Emissions test func-
tion (see page 106)
b5
Control mode
b6
Constant mode
b7
Boiler water tem-
perature regulated
by control thermo-
stat "R"
b8
Control mode
bC
Control mode with-
out remote control
62
Cause
Measures
Return tempera-
Insert plug aJA and
ture control con-
check coding
figuration fault:
Code "OC:1" has
been selected,
but plug aJA is
not plugged in
and/or
Code "4E:0" has
not been set
Flue gas tem-
Check the flue gas tem-
perature sensor
perature sensor (see
shorted out
page 113)
Communication
Check connections and
fault, program-
replace the program-
ming unit
ming unit, if required
Internal electro-
Check the electronics
nics fault
PCB and replace, if re-
quired
Internal electro-
Check the electronics
nics fault
PCB and replace, if re-
quired
Invalid hardware
Check coding address
recognised
"92"; "92:164" must be
selected
Boiler coding card
Plug in the boiler coding
fault
card or replace if faulty
(see page 18)
Flue gas tem-
Check the flue gas tem-
perature sensor
perature sensor (see
lead broken
page 113).
Without flue gas tem-
perature sensor:
Set code "1F:0"
Communication
Check connections,
fault
Vitotrol re-
cable, coding address
mote control,
"A0" and remote control
heating circuit A1
DIP switches (see
page 115 and 116)
(cont.)