Heating circuit control
Party and economy keys on all control
units have no function.
Frost protection
In the case of outside temperatures
below +1 ºC a minimum flow tempera-
ture of 10 ºC is ensured. For changes
see coding address "A3", variable
frost limit.
Therm-Control
The output is reduced if the actual
temperature at the Therm-Control
sensor falls below the set tempera-
ture. This connects the mixer of down-
stream heating circuits.
Raising the reduced room temperature
During operation with reduced room
temperature, the reduced set room
temperature can be automatically
raised subject to the outside tempera-
ture. The temperature is raised in
accordance with the selected heating
curve, but no higher than the set stan-
dard room temperature.
(cont.)
The outside temperature limits for the
start and end of the temperature rais-
ing can be adjusted via coding
addresses "F8" and "F9".
Function description
73