Viessmann Vitotronic 200 Installation And Service Instructions Manual page 63

Table of Contents

Advertisement

Faults that are displayed at the programming unit
Fault code
System character-
on the dis-
istics
play
bF
Control mode
C1
Boiler cools down
C2
Control mode
C4
Control mode
C8
Boiler cools down
C9
Boiler cools down
CA
Boiler cools down
Cb
Boiler cools down
Cause
Measures
Incorrect LON
Replace LON communi-
communication
cation module (see
module
page 107)
External safety
Check plug aBÖ and ex-
device
ternal safety equipment
(see page 26)
KM BUS connec-
Check KM BUS cable
tion lead broken
and the solar control
to solar heating
unit.
control unit
Without solar control
unit:
Set code "54:0"
Communication
Check connections and
fault, function ex-
cables/leads; if required
tension 0 - 10 V
replace the function ex-
tension (see page 118).
Without function exten-
sion:
Set code "9d:0"
Low water indica-
Check the water level of
tor fault
the system; reset low
water indicator (see
page 121)
Maximum pres-
Check the system pres-
sure limiter fault
sure; reset the maxi-
mum pressure limiter
(see page 121)
Minimum or maxi-
Check system pressure,
mum pressure
reset minimum or maxi-
limiter 2 faults
mum pressure limiter 2
(see page 121)
Additional high
Check the system tem-
limit safety cut-
perature; reset the high
out fault
limit safety cut-out or
or
flue gas damper (see
Temperature limit-
page 121)
er
or
Flue gas damper
Troubleshooting
(cont.)
63