System controller configuration

Alarm email settings

Call up with
å
"Configuration"
"Configuration"
"Parameter system controller"
"Settings alarm email"
Fig. 26
These parameters must be determined and set by the
operator.
An email account must be created with an email pro-
vider.
The account details must be specified here.
(cont.)
Note
The Saia PLC can only send unencrypted emails.
With most email providers, this is no longer possible.
With many email providers, the "HP designation
(sender email address)" and "Email acc. name"
must be identical.
"Email provider IP address"
The IP address (not the name) of the email server
must be specified.
"Email subject (HP ID)"
Text here can be entered as required. It can be used
to identify heat pumps, e.g. "Alarm HP no. 123
Worb"
Configuring the system