Viessmann Vitotronic SPS Service Instructions Manual page 27

Hide thumbs Also See for Vitotronic SPS:
Table of Contents

Advertisement

System parameters
"Response delay flow switch"
The response time of the flow switch.
"Condenser pump run-on time"
The period during which the secondary pump contin-
ues to run after heat pump operation, so that the
heat can be transferred.
"Maximum return temperature secondary circuit"
Maximum condenser inlet temperature
"Min. return temperature primary circuit"
Minimum evaporator outlet temperature during cool-
ing mode
"Output contrllr min"
Minimum value of the output controller; see "Notes
on output controller"
"Output contrllr multiplier"
Multiplier for output control; see "Notes on output
controller"
"Time limit f. partial output"
Period after which the system is switched to the
other compressor in single stage operation
"Minimum limit evaporation temperature"
Minimum value of evaporation temperature in refrig-
erant circuit; see "Notes on application limit"
"Minimum limit evaporator outlet"
Minimum temperature at evaporator outlet during
heating mode; see "Notes on application limit"
"Maximum temp re-cooling via heat source"
The highest temperature that can be returned to the
heat source.
Note
In the case of geothermal probes, a maximum of
30 °C may be fed into the probe.
"Maximum limit condensation temperature"
The maximum condensation temperature in the
refrigerant circuit; see "Notes on application limit"
"Alarm time limit for failure due to appl. limits"
Time limit for alarm detection in 1/10 hr
Example:
Set value: 5 = 5/10 hr = 0.5 hr = 30 minutes
"Alarm number limit for failure due to appl. lim-
its"
Number of alarms that must occur during the pro-
grammed period to trigger an alarm.
(cont.)
Buttons:
"Confirm!"
"Back"
One page back
Notes on application limit
Note
It is possible to set the parameters "Minimum limit
evaporation temperature", "Minimum limit evapo-
rator outlet" and "Maximum limit condensation
temperature" such that the compressors, depending
on the type of heat pump, will run outside the applica-
tion limits. During configuration (especially with ice
store systems), care must be taken that at evaporation
temperatures of < 0 °C, the parameter "Maximum
limit condensation temperature" is adjusted down-
wards.
Note
The system application limits (see technical guide)
must be observed. The parameters must be configured
in such a way that this will be the case for all operating
situations. If in doubt, consult Viessmann on this mat-
ter.
Notes on the output controller
Formula for calculating the set output
x = "Actual temperature at condenser outlet" minus
"Condenser spread"
or
"Actual temperature at condenser re-entry",
depending on which value is greater
Set output = (Set temperature + 1 °C - x) * Output
controller factor
Calculated set outputs of over 100 % result in 100 %
output demand.
For certain configurations, the minimum output
demand is limited to 5 %. The prevents the output con-
troller from switching the system off unnecessarily.
Configuring the system
27