Configuring the system
System parameters
Examples
260
240
220
200
180
160
140
120
100
80
60
40
20
0
0
1
2
3
Fig. 19
Example
Set temperature
(heating water buffer
cylinder)
D
Output controller fac-
tor
B
Actual temperature
C
Condenser spread
A
Set output
E
Explanation
Examples 1 to 4:
The set output falls because the actual temperature is
approaching the set temperature.
Examples 5 and 6:
The set output rises because the output controller fac-
tor has been adjusted.
Examples 7 to 9:
The set output changes because the condenser
spread changes.
Examples 9 and 10:
28
(cont.)
4
5
6
7
1
2
°C
50
50
50
15
15
15
°C
40
42
44
K
2.0
2.0
2.0
%
165
135
105
8
9
10
11
3
4
5
6
50
50
50
15
30
60
46
46
46
2.0
2.0
2.0
75
135
255
The set output changes because the output controller
factor changes.
Examples 10 and 11:
The set output changes because the differential
between the set temperature and actual temperature
changes.
General:
The condenser spread is effective only if the spread is
no greater than 2 K. If the spread is less than 2 K in
the condenser, the set output is reduced. Where the
spread is greater than 2 K, the set output is deter-
mined from the temperature at the condenser re-entry.
7
8
9
50
50
50
15
15
15
46
46
46
1.0
0.5
2.0
2.0
60
52.5
75
10
11
50
50
5
5
46
40
2.0
35
65