Troubleshooting
Overview of fault messages
TID
Pp. No. Fault message
55
"Alarm, flow weak, evapo-
rator"
56
15
"No flow in groundwater
circuit"
57
"PLC"
58
"Dry cooler (209)"
59
5
"Evaporator pump"
60
"Flow temperature too low
circuit 1"
61
"Flow temperature too low
circuit 2"
62
"Flow temperature too low
circuit 3"
63
"! ! ! Emr_off_actv ! ! !"
70
"Low press. (transmitter)"
48
(cont.)
Effect
The heat pump is switched
off
The heat pump is switched
off
Possible faulty control char-
acteristics in the heat pump
control unit
The heat pump cannot dissi-
pate its heat sufficiently in ac-
tive cooling mode. This cau-
ses high pressure or super-
heating faults.
Evaporator pump and heat
pump switch off
The heating circuit pump for
heating circuit 1 is switched
off
The heating circuit pump for
heating circuit 2 is switched
off
The heating circuit pump for
heating circuit 3 is switched
off
The heat pump is switched
off
All compressors are switched
off
Cause
Flow rate through evaporator
too low, ΔT inlet/outlet > 10 K.
Evaporator contaminated
Circulation pump faulty
A shut-off damper is closed
Flow rate through system sep-
arator too low
System separator contami-
nated
Filter contaminated
Well pump faulty
A shut-off damper is closed
Groundwater level too low
A control unit problem has oc-
curred
Fan, control unit or speed
controller of re-cooler faulty
Re-cooler contaminated
Contactor for evaporator
pump is not functioning
Frost protection switch has
responded
Safety high pressure switch
has responded
The control unit is not func-
tioning correctly for cooling.
The set minimum value has
been undershot.
The control unit is not func-
tioning correctly for cooling.
The set minimum value has
been undershot.
The control unit is not func-
tioning correctly for cooling.
The set minimum value has
been undershot.
The external emergency stop
button has been operated.
To acknowledge:
Reset the switch and then ac-
knowledge in the alarm list.
Pressure on the low pressure
side has fallen below the mini-
mum permissible level.
No pressure could be built up.
Circulation pump faulty or
flow rate too low
No circulation through evap-
orator
Expansion valve faulty
Too little refrigerant in refrig-
erant circuit