Conditions for enabling and automatic starting of heat pump

If the "Enable heat pump" display is not active
(green), the heat pump cannot switch on.
52
(cont.)
Effect
Compressor 1 is switched off
Compressor 2 is switched off
Compressor 1 is switched off
Compressor 2 is switched off
Cause
Temperature in compressor
too high
Superheating at expansion
valve EEV too high
Lack of refrigerant
Primary and/or secondary
temperature too high
Temperature in compressor
too high
Superheating at expansion
valve EEV too high
Lack of refrigerant
Primary and/or secondary
temperature too high
Hot gas temperature at com-
pressor outlet too high
Compressor has too little oil.
Superheating at expansion
valve EEV too high
Lack of refrigerant
Primary and/or secondary
temperature too high
Hot gas temperature at com-
pressor outlet too high
Compressor has too little oil.
Superheating at expansion
valve EEV too high
Lack of refrigerant
Primary and/or secondary
temperature too high