Troubleshooting; Alarm Sounds And 12.2 Electricity Returned But; Battery Test Failed; The Ups - Gamatronic MEGA V2 SA25 User Manual

25 kva / 25 kw double-conversion ups 3x400 vac with true on-line battery
Table of Contents

Advertisement

12. T
ROUBLESHOOTING
This section explains what to do in the event of an alarm condition, or when any other "out of the
ordinary" event occurs on the UPS.
12.1
Alarm sounds and/or Alarm LED lights up
1.
Go to the Event Log and look at the Active Alarm Display to determine the nature of
the alarm. See "Navigating to the event log" and "Active alarm display" on page 25.
2.
Look for the appropriate heading below according to the nature of the alarm, and follow the
instructions.
12.2
Electricity returned but UPS remains in Battery Mode
Check the external circuit breaker for the AC line. The circuit breaker may be off.
12.3

Battery Test failed

It may be that an automatically scheduled battery test was executed shortly after the end of a
power outage, when the battery was still charging. Wait until about two hours after the return of
the AC power and perform a manual battery test. This should clear the alarm.
12.4
The UPS remains in bypass mode
The UPS may have been put in bypass mode manually. In such a case, the lower left quadrant
of the main screen says "manual bypass". To manually return the UPS to normal mode, see
"Manually entering or leaving bypass mode" on page 47
12.5

Sync Fault

Verify that the ac input and the bypass Input lines are connected to the UPS in proper phase
sequence.
Verify that ac of the proper frequency (Hz) is being used. (See on page 58.)
52
Gamatronic Electronic Industries Ltd.
User Guide: MEGA V2 SA25, Release 1.5

Advertisement

Table of Contents
loading

Table of Contents