Power Module - Huawei UPS5000-E Series User Manual

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(350 kVA–800 kVA)
User Manual (50 kVA Power Modules)

2.3.3 Power Module

Appearance
Figure 2-19 Power module
(1) Positioning lock
(5) Ready switch
Table 2-2 Indicator description
Indicator
Run
indicator
Issue 15 (2022-01-30)
(2) Run indicator
(6) Output port
Color
Status
Green
Steady
on
Blinking
slowly
Blinking
fast
Copyright © Huawei Technologies Co., Ltd.
(3) Alarm indicator
(7) Input port
Description
The system is working in inverter mode.
● The inverter is ready and in standby state
(blinking at 0.5 Hz, on for 1s and off for
1s).
● The inverter is not started (blinking at 0.2
Hz, on for 2.5s and off for 2.5s).
The module is not configured, the inverter
software and rectifier software are being
upgraded, or the inverter software is being
upgraded (blinking at 4 Hz, on for 0.125s and
off for 0.125s).
2 Overview
(4) Fault indicator