UPS5000-E-(350 kVA–800 kVA)
User Manual (50 kVA Power Modules)
Safety and EMC
EMC

7.5 Mains Input Electrical Specifications

Item
Input system
Rated input voltage
Input voltage
Rated frequency
Input frequency
Input PF
THDi

7.6 Bypass Input Electrical Specifications

Item
Input system
Issue 15 (2022-01-30)
Specifications
EN 62040-2
IEC 62040-2
IEC 61000-2-2
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-5
EN 61000-4-3
EN 61000-4-6
IEC 61000-4-8
Specifications
Three-phase, four-wire, and PE. If current is allowed in
the PE wire, input without the N wire is supported.
380 V AC, 400 V AC, or 415 V AC (line voltage)
● 80–280 V AC (phase voltage)
● At 40°C: The UPS works at full load when the voltage
is 187–280 V AC and is derated to 40% load when
the voltage is 187–80 V AC.
● At 30°C: The UPS works at full load when the voltage
is 176–280 V AC and is derated to 40% load when
the voltage is 176–80 V AC.
50 Hz/60 Hz
40–70 Hz
● > 0.99 (full load)
● > 0.98 (half load)
● THDi ≤ 3% (full linear load)
● THDi ≤ 5% (full non-linear load)
Specifications
Three-phase, four-wire, and PE
Copyright © Huawei Technologies Co., Ltd.