UPS5000-E-(350 kVA–800 kVA)
User Manual (50 kVA Power Modules)
Figure 4-20 EPO ports
After you press the EPO button, the EPO and No power supplied alarms are
displayed on the LCD.
4.10 Clearing the EPO State
Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the dry contact is
not in the EPO state.
Step 2 Clear the EPO alarm in the system.
●
●
●
Step 3 View active alarms and check that the EPO alarm is cleared. If the system bypass
input is normal, the UPS transfers to bypass mode.
●
●
●
Step 4 Start UPS inverters.
----End
4.11 Exporting Data
Issue 15 (2022-01-30)
On the LCD
Choose System Info > Alarms and tap Clear Faults. In the displayed dialog
box, tap Yes to clear the EPO alarm.
On the WebUI
Choose Monitoring > UPS System > Running Control and click Clear Fault.
The EPO alarm is cleared.
On the old WebUI
Choose Monitoring > Control > System Commands and Tests and click
Clear Faults. The EPO alarm is cleared.
On the LCD
Choose System Info > Alarms > Active Alarms to check that the EPO alarm
has been cleared.
On the WebUI
Choose Home > Active Alarm to check that the EPO alarm has been cleared.
Viewing active alarms on the old WebUI
Choose Monitoring > Active Alarms and check that the EPO alarm has been
cleared.
Copyright © Huawei Technologies Co., Ltd.
4 Operations
161