2.11.3 Manual Management

OnCuer Plus allows remote control of items in your
home. Electrical items such as appliances, outdoor
lighting, storm shutters, etc. can be connected to
outputs on the generator set's programmable interface
module (PIM) and then turned on and off using OnCue
Plus through your personal computer, smart phone,or
tablet with Internet access.
Controlling items remotely requires an installed and
properly connected Programmable Interface Module
(PIM). The programmable interface module (PIM) is
available for purchase as an optional kit.
The PIM provides two programmable inputs and six
programmable
outputs
customer-supplied equipment. The PIM operates only
with generator sets equipped with the Kohler RDC2,
DC2, or VSC controller.
installation and setup instructions.
Note: PIM outputs 1 and 2 are factory-set to Generator
Running and Common Fault. Outputs 1 and 2
cannot be controlled remotely through OnCuer
Plus.
Use the Controls screen to remotely control items in
your home connected to outputs 3 through 6.
1. Select the Controls screen in the OnCue Plus
Toolbar.
2. Click on the name of the output to turn it on or off.
The status indicator (ON/OFF) flashes for
approximately 5 seconds before changing to the
new status.
Figure 2-17 Controls, Automatic Management
30
Section 2 OnCue Plus Operation
for
connection
to
See TT-1584 for PIM
Once OnCue Plus is used to turn a PIM output on or off,
the output will no longer be controlled by the generator
set. For example, output 4 may initially be set to the
generator function Not in Auto. If OnCue Plus is used to
turn that output on or off, the output will no longer
operate when the generator's Not in Auto function
operates. The output must be operated through OnCue
Plus.
Use OnCue Plus to rename the output functions to
identify the equipment connected to each output. See
Section 2.14, Settings, for label renaming instructions.
Figure 2-16 Manual Management

2.11.4 Automatic Management

Automatic management displays the status of items
connected to the load control module (LCM) or load
shed kit. Non-essential loads connected to the load
control relays are disconnected automatically when
essential equipment is running to prevent generator set
overload. The item descriptions can be edited through
the Settings view. See Section 2.14.