Controls; Start Exercise - Kohler OnCue Plus RDC Operation

Table of Contents

Advertisement

2.11 Controls

From the Controls view, you can:
Start and stop a generator exercise
D
View the status of outputs connected to the PIM or
D
LCM
Turn outputs connected to the PIM on and off.
D
The generator set controller must be in AUTO mode for
remote start/stop using OnCue Plus.

2.11.1 Start Exercise

An unloaded cycle exercise or an unloaded full speed
exercise can be started remotely.
Unloaded Full-Speed Exercise. Runs the generator
D
set at full speed without transferring the load from
utility. The model VSG generator set runs at rated
no-load speed.
Unloaded Cycle Exercise. Runs the unloaded cycle
D
exercise with complete system diagnostics. See
generator set Operation Manual for information about
the unloaded cycle exercise and diagnostics.
1. Click to start an exercise.
Figure 2-14 Controls, Start Exercise
28
Section 2 OnCue Plus Operation
Click Start to start the generator set. The dialog box
shown in Figure 2-13 opens. Select the exercise type
and click on START.
The exercise runs for 20 minutes (default setting) and
then stops. Use the Stop Exercise command to stop the
engine earlier, if necessary.
The Start Exercise options are unscheduled. Starting
and stopping the engine using these commands does
not change the exercise schedule on the generator set.
Figure 2-13 Select Exercise Type
1
TP-6928 1/14