Controller Password And Serial Number; Rdc2 And Vsc Controller Password And Serial Number; Dc2 Controller Password And Serial Number; Rdc/Dc Controller Password - Kohler OnCue Plus RDC Operation

Table of Contents

Advertisement

1.9 Controller Password and
Serial Number
The generator serial number and the controller
password for the RDC2 or VSC controller are required
for the OnCue Plus application.
Perform the password reset procedure before
connecting the generator set's Ethernet cable to the
router. If the generator set is connected to the Internet
before the password is set at the controller, you will need
to cycle power to the controller after setting the
password.
Note: A new password is generated each time the reset
password procedure is performed.
If the password is reset after the OnCue Plus system has
been set up, the connection will be lost. Disconnect the
battery power to the controller, wait a minute, and then
reconnect the power. Re-enter the time, date, and
exercise schedule on the controller after the power is
reconnected.
1.9.1
RDC2 and VSC Controller
Password and Serial Number
Be ready to write down the serial number and password.
The serial number (S/N) and password are displayed for
10 seconds. Follow this procedure to obtain the serial
number and password:
1. Press the controller's down arrow button to
navigate to the Networking Information menu.
2. Follow the reset password procedure shown in
Figure 1-7.
See the generator set operation
manual for more information, if necessary.
3. Write down the serial number (S/N) and password.
1.9.2
DC2 Controller Password and
Serial Number
Be ready to write down the serial number and password.
The serial number (S/N) and password are displayed for
TP-6928 1/14
10 seconds. Follow this procedure to set the OnCue
Plus password on the DC2 controller:
1. Press the OFF button and verify that the generator
set is not running.
2. Press and hold the Exercise button until Press
Again to Reset OnCue Plus PW is displayed.
3. Release the Exercise button and press it again
within 5 seconds.
Note: If the Exercise button is not pressed within 5
seconds, the controller exits the password
reset mode.
4. Write down the serial number (S/N) and password.
1.9.3

RDC/DC Controller Password

The password may have been recorded during the
installation of the Ethernet option board on the
generator set controller. See TT-1566 or the procedure
below.
Be ready to write down the password. The four-digit
password will be displayed for 10 seconds. Follow this
procedure to obtain the serial number and password:
1. Press the OFF button to place the controller into
OFF mode.
2. Press the down arrow button (RDC) or exercise
button (DC) 5 times. Note the four-digit code
displayed on the controller. This is the controller
password.
3. Write down the password to enter into OnCue Plus.
4. Press OFF to clear the display.
Note: Do not repeat this procedure after the password
has been entered into OnCue Plus.
The controller password changes each time this
procedure is performed. If the controller is connected to
OnCue Plus and this procedure is performed again, the
connection will be lost.
Section 1 System Information and Installation
15

Advertisement

Table of Contents
loading

Table of Contents