Kohler OnCue Plus RDC Operation page 25

Table of Contents

Advertisement

Status Screen Item
Name
Name of generator that you are
monitoring
Generator status
The status of the generator that
message
you have selected
Time
Time of the last update
GEN Symbol
Generator Status
Power Line Symbol
Utility power status
Home Symbol and
Home does or does not have
home status message
power
Total Power
Power being supplied to the
home, in kW (LCM required)
Battery Voltage
Generator engine starting battery
voltage
Figure 2-9 Status Screen Displays
TP-6928 1/14
Indicates
Select the generator from the list on the left side of the screen.
(Click on the arrow symbol to reveal the list.)
Examples of status messages are "Generator Running" and
"Standby." If a fault condition is indicated, check the Event
History view or the controller display to identify the fault.
The frequency of updates can be changed through the Settings
screen.
Green when active, gray when not available.
Green when active, gray when not available.
Symbol is green when the home has power from either the
generator or utility.
Gives an indication of how much power is being used, allowing
power management through OnCue Plus.
Typically 12--15 volts DC. A voltage below 12.5 VDC will
trigger a low battery voltage warning, indicating that the battery
should be charged or replaced. A voltage less than 11 volts
DC will be displayed in red.