TROUBLESHOOTING REFRIGERATION SYSTEM
Trouble
3. Compressor operates
continuously but does not
form sufficient ice bank.
4. Agitator motor not operat-
ing.
© 2002, IMI Cornelius Inc.
Probable Cause
A. Cooling capacity is
exceeded by over-draw-
ing.
B. Dispenser located in
excessively hot area or
air circulation through
condenser coil is
restricted.
C. Problem with sealed
refrigeration system.
A. No power source (blown
fuse or tripped circuit
breaker).
B. Agitator motor propeller
obstructed.
C. Low voltage.
D. Loose, disconnected, or
broken wiring.
E. Inoperative agitator
motor.
- 25 -
Olympus Post-Mix Service Manual
Remedy
A. Reduce amount of drinks
drawn per given time.
B. Relocate dispenser or
check and if necessary,
clean condenser coil as
instructed.
C. Service or replace sys-
tem.
A. Replace fuse or reset cir-
cuit breaker. (NOTE:
Fuse or circuit breaker
are not part of the dis-
penser).
B. Remove obstruction.
C. Voltage must be 90–135
VAC (115 volt unit or
180–260 (230 VAC unit)
at compressor terminals
when compressor is try-
ing to start.
D. Tighten connections or
replace broken wiring.
E. Replace agitator motor.
Publication Number: 750300229