DSC T-Link TL300 Installation Manual page 24

Network internet alarm communicator
Table of Contents

Advertisement

[034] Trouble Toggle Option Section 2
Toggle
[1]
[2]
[3]
[4]
[5]
[6]-[8]
[035] PGM1 Enable/Disable
Default: 01
This PGM can be enabled (01) or disabled (00).
When the PGM is enabled, the output will activate when any of the trouble conditions enabled in
the T-Link Trouble Toggle Options are present. It will deactivate when all the selected trouble
conditions are cleared.
NOTE: If a trouble condition occurs that is not enabled in the T-Link Trouble Reporting option, the PGM will
not turn on for that trouble condition nor will it be required to turn off the PGM.
PGM1- The PGM1 output is dedicated for
TL250 trouble indications. Program this option as '01'
for Modes 2 & 3.
If a control panel is not monitoring the T-Link TL250, an
LED or a buzzer can be connected between this terminal
and the RED terminal for trouble indication. The PGM
terminal switches low from an open-collector state.
NOTE: The PGM output can sink 50mA (max.). For UL
installations, use DSC RM-1 Relay Module.
PGM2- The PGM2 output is dedicated as an input fol-
lower that is triggered on any input alarm (including Bell
Follower which generates Burglary and Fire Alarms)
except for keyswitch zones. The PGM2 output will only
turn off when ALL violated zones are restored.
NOTE: PGM2 is always enabled and follows all zones. It is
the users option to connect devices to the PGM.
[036]-[047] Digital input 1 through 12 configuration for the T-Link TL250
Default: 00
Program a 2-digit code for the definition of the inputs. Select a definition from the list below.
[00] Null Input
The input is vacant. Unused inputs should be programmed as Null inputs. Any activity on this
input is ignored.
[03] Instant Input
This input type will report if the T-Link TL250 is armed, it also supports force arming. When
forced armed the TL250 will arm even if the input is open. When the input is closed it is treated
as a normal instant input. SIA Reporting Code: BA/BH.
[08] Standard 24-hr. Fire Input
When this input is violated, the panel immediately communicates to the central station. SIA
Reporting Code: FA/FH.
[11] Standard 24-hr. Burglary
When this input is violated, the panel immediately communicates to the central station. SIA
Reporting Code: BA/BH.
[16] 24hr Panic Input
If this input is violated, when the system is armed or disarmed, the panel reports to the central
station. SIA Reporting Code: PA/PH.
Default
OFF
| _ ___________|
OFF
| _ ___________|
OFF
| _ ___________|
OFF
| _ ___________|
OFF
| _ ___________|
| _ ___________|
Description
FTC to Receiver 2
Keyswitch Arm/Disarm Reporting
T-Link Remote Programming
T-Link Local Programming
Receiver 2 Absent
For Future Use
T-Link
LED Output with
current limiting
resistor
Optional rela y
driver output
20
T-Link TL250
RED
BLK
YEL
GRN
LED
560
To External
Supply
+
Coil
Relay
NC
Com
COM
PGM
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

T-link tl250T-link tl300cf

Table of Contents