DSC T-Link TL300 Installation Manual page 22

Network internet alarm communicator
Table of Contents

Advertisement

[013] Receiver #2 T-Link Source Port Number
Default: 3065 (0BF9
[014] Receiver #2 T-Link Destination Port Number
Default: 3061 (0BF5
[015] Receiver #3 IP (Static IP address for the third receiver)
Default: 000 000 000 000
Program the IP address of the third receiver.
[016] Receiver #3 Gateway
Default: 000.000.000.000
This is the IP address of the local gateway the T-Link TL250/TL300 can use to connect with
the third receiver (WAN network). The IP address of the gateway must also be a valid IP
address for the local subnet.
[017] Receiver #3 T-Link Source Port Number
Default: 3066 (0BFA
[018] Receiver #3 T-Link Destination Port Number
Default: 3061 (0BF5
[019] Console Port Number
Default: 3064 (0BF8
[020] TFTP Port
Default: 69 (0045
Port used to do the remote flash upload.
[021] DLS Port Number
Default: 3062 (0BF6
[022] SA Port Number
Default: 3063 (0BF7
[023] T-Link Supervision Enable/Disable
Default: 0
When set to 1, the T-Link TL250/TL300 is supervised by the central station receiver.
NOTE: For UL/ULC installations, this option must be set to 1.
[024] Receiver Failure Debounce Time
The amount of time that must elapse with no heartbeat response from the receiver before the
T-Link TL250/300 will generate a Receiver #1 absent condition.
NOTE: For UL installations, this option shall be set to B4h (180s). For ULC installations this option shall be
set to 5Ah (90s) for Security Level 4, and to 4Bh (75s) for Security Level 5.
[025] Receiver Restoral Debounce Time
The amount of time that must elapse when the heartbeat resumes from the receiver before the
T-Link TL250/300 will generate a Receiver #1 restoral condition.
[026]-[027] E-mail Address 1 and 2 (64 characters max.)
Default: None
The T-Link TL250/TL300 can send alarm messages to two E-mail addresses. The TL250/TL300
only supports SMTP to transmit E-mails in the MIME format. The TL250/TL300 does not support
UUENCODE message formats. The TL250/TL300 does not accept any incoming messages.
NOTE: This option can only be programmed via the console software.
The following is an example of the information contained in an E-mail from the TL250/TL300
module. For more details on SIA reporting codes, refer to the control panel Installation Manual.
From: T-Link 123456
To: recipient@address.com
Subject: T-Link v1.0.30; 123456 Event Report
Message: #6789|[Nri0/LS000]
NOTE: The account number in the subject line is the T-Link's account number. The account number in the
message body is from the originator of the signal. In this example, the originator was the panel connected on
the PC-Link with account number 6789. If the T-Link would have been the originator, the account number in
the message body would match the account number in the subject line.
Hex
)
Hex
)
Hex
)
Hex
)
Hex
)
Hex
)
Hex
)
Hex
)
18

Advertisement

Table of Contents
loading

This manual is also suitable for:

T-link tl250T-link tl300cf

Table of Contents