Section 4
Setfile (REB500 Configuration File)
116710_A.mdb
1167
10
_A
.mdb
Remark: File version index and revision index are automatically added to the file name (see
5.1.2).
4.1.2

Project directory structure

A REB500 set file configured with the HMI500 Configurator mode has to be saved in a REB500
project structure. For ABB in-house configured systems, the following projects structure is used:
IEC18000565 V1 EN-US
Figure 3:
1-File-configuration (draft version)
In this directory, the setfile is temporarily stored during the configuration phase. It has to be
moved to 2-File-Testing, after setfile configuration has finished.
2-File-testing (test version)
While testing/commissioning the system, the setfile is saved under this directory. After the
system tests/ commissioning have finished, the file has to be moved to 3-File definitive.
3-File-definitive
This is the place for a setfile of a REB500 in service. The directories 1-File-configuration and 2-File-
Testing should be empty now.
4-File-old-versions
If a system (setfile) is modified (re-configured), it is recommended to store the old version(s) of
the setfile under this directory. This folder contains the history of all versions, which had been
applied during the lifetime of a REB500/REB500sys system.
14
System number
provided by ABB
File version index
This index is defined by the user, for example:
01 = 0.1 → preliminary setfile
10 = 1.0 → setfile version for commissioning
Revision index
The file revision index (A, B, up to AY, AZ) should be defined
by the client engineer on site by using the HMI500 program.
File extension
The extension .mdb, which is mandatory, is added
automatically
IEC18000565-IEC18000565-1-en.vsdx
Directory structure REB500 setfiles