GETTING STARTED (continued) 
Getting Around: 
LVU800 Series is configured by the use of three push buttons (UP, DOWN and SELECT) and a LCD display.  As a 
lockout  feature,  the  buttons  are  inactive  until  the  SELECT  button  is  held  down  for  5  seconds,  and  then  the 
display will begin to scroll through the top level of the configuration menu. 
Steps for Basic Configuration: 
1. Select and Set the units of operation in the UNITS menu. 
2. Configure the Sensor Height and Fill‐H under the TANK menu. 
3. Set the SAFE value. 
Top Level 
 The Configuration menu will continue to scroll through the items below until the SELECT button is pressed.   
 UNITS – TANK – SAFE – TG CAL – VALUES ‐ HELP – RUN. 
 To return to the Operational mode of LVU800 Series, press SELECT while RUN appears in the display. 
 UNITS  –  Allows  end  user  to  select  the  units  for  configuration  and  operation.    Select  between  Inches, 
Centimeters, Feet, Meters or Percent.  Press EXIT to return to the Top Level menu. 
 TANK – Allows the end user to configure the operational range for the switch.   
o HEIGHT – Distance from the transducer face to the bottom of the tank. 
o FILL‐H – Maximum fill height of the liquid from the bottom of the tank. 
o REV MA – Allows the transmitter to reverse the current output such that 4 mA is at FULL and 20 
mA is at EMPTY. 
o Press Exit to return to the Top level Menu. 
o Note: if UNITS is set to Percent, then TANK will not appear.  To view TANK, set UNITS to any of the 
following: Inches, Centimeters, Feet or Meters. 
 SAFE – The fail‐safe for the LVU800 Series can be preset to the customer's requirement. 
o 22 mA – Overfill fail‐safe setting. 
o 21 mA – Overfill fail‐safe setting. 
o 20 mA – Full fail‐safe setting. 
o 4 mA – Empty fail‐safe setting. 
o HOLD – Keeps the output at its last current reading when fail‐safe condition occurs. 
 TG CAL – Target Calibration (allows for the sensor to accept the current level as either EMPTY or FULL. 
 VALUES – Provides setup information, the ability to reset the LVU800 Series and a simulation mode to test 
the relay function. 
o SETUP – Will display the setting for all functions of LVU800 Series. 
o DIAG  –  This  is  a  production  test  feature  used  by  the  factory  to  confirm  operation.    This  mode 
should only be used when supervised by an Omega Engineering representative. 
o RESET – Will reset the LVU800 Series back to its original factory setting. 
 HELP – Provides information for contacting Omega Engineering no‐line. 
 RUN – Returns the unit to normal measurement and control mode. 
 
 
 