GETTING STARTED (continued)
Getting Around:
LVU800 Series is configured by the use of three push buttons (UP, DOWN and SELECT) and a LCD display. As a
lockout feature, the buttons are inactive until the SELECT button is held down for 5 seconds, and then the
display will begin to scroll through the top level of the configuration menu.
Steps for Basic Configuration:
1. Select and Set the units of operation in the UNITS menu.
2. Configure the Sensor Height and Fill‐H under the TANK menu.
3. Set the SAFE value.
Top Level
The Configuration menu will continue to scroll through the items below until the SELECT button is pressed.
UNITS – TANK – SAFE – TG CAL – VALUES ‐ HELP – RUN.
To return to the Operational mode of LVU800 Series, press SELECT while RUN appears in the display.
UNITS – Allows end user to select the units for configuration and operation. Select between Inches,
Centimeters, Feet, Meters or Percent. Press EXIT to return to the Top Level menu.
TANK – Allows the end user to configure the operational range for the switch.
o HEIGHT – Distance from the transducer face to the bottom of the tank.
o FILL‐H – Maximum fill height of the liquid from the bottom of the tank.
o REV MA – Allows the transmitter to reverse the current output such that 4 mA is at FULL and 20
mA is at EMPTY.
o Press Exit to return to the Top level Menu.
o Note: if UNITS is set to Percent, then TANK will not appear. To view TANK, set UNITS to any of the
following: Inches, Centimeters, Feet or Meters.
SAFE – The fail‐safe for the LVU800 Series can be preset to the customer's requirement.
o 22 mA – Overfill fail‐safe setting.
o 21 mA – Overfill fail‐safe setting.
o 20 mA – Full fail‐safe setting.
o 4 mA – Empty fail‐safe setting.
o HOLD – Keeps the output at its last current reading when fail‐safe condition occurs.
TG CAL – Target Calibration (allows for the sensor to accept the current level as either EMPTY or FULL.
VALUES – Provides setup information, the ability to reset the LVU800 Series and a simulation mode to test
the relay function.
o SETUP – Will display the setting for all functions of LVU800 Series.
o DIAG – This is a production test feature used by the factory to confirm operation. This mode
should only be used when supervised by an Omega Engineering representative.
o RESET – Will reset the LVU800 Series back to its original factory setting.
HELP – Provides information for contacting Omega Engineering no‐line.
RUN – Returns the unit to normal measurement and control mode.
8