Troubleshooting - Omega LVU800 Series User Manual

Hide thumbs Also See for LVU800 Series:
Table of Contents

Advertisement

APPENDIX 

Troubleshooting:

PROBLEM 
TANK does not appear on 
the main menu: 
Display shows FULL: 
Display shows EMPTY: 
Display shows WARMUP: 
Display shows LOST: 
Display is opposite of the 
measured value: 
Transmitter indicates a 
current of 0 mA: 
Transmitter jumps to a 
current reading between 
19 and 20 mA: 
Transmitter indicates a 
current over 23 mA: 
 
 
 
 
Units  function  is  set  for  PERCENT  on  LVU800  Series:  
When  Units  is  set  for  PERCENT,  the  TANK  function  is 
disabled.    To  re‐enable  TANK,  change  units  to  INCHES, 
CM, FEET or METERS. 
Level  of  liquid  is  above  the  FILL‐H  setting:    Check  the 
FILL‐H  setting,  making  sure  the  FILL‐H  setting  is  high 
enough so the level of liquid is below the FILL‐H setting.  
The Fill‐H setting is the distance from the bottom of the 
tank to the Full level of liquid. 
Level of liquid is beyond the HEIGHT setting:  Check the 
HEIGHT  setting,  making  sure  the  HEIGHT  setting  is  low 
enough  so  the  level  of  liquid  is  above  the  HEIGHT 
setting. 
Typically  occurs  when  power  is  being  applied  to 
transmitter.    Indicates  a  weak  power  supply,  bad  wire 
connections  or  the  sensor  is  out  of  the  operational 
range.  
Sensor  is  in  a  Fail‐Safe  state.    The  return  sound  pulses 
are  not  reaching  the  transducer.    First,  cycle  power  off 
and  on,  waiting  5  seconds  between  the  off  and  on 
states.  If problem persists, check the installation fitting 
against the Installation instructions in the manual. 
Check  the  DISPLAY  setting.    AIR  mode  indicates  the 
distance  from  the  liquid  to  the  sensor.    LIQUID  mode 
indicates  the  height  of  liquid  in  the  tank.    Change  the 
DISPLAY  mode  from  AIR  to  LIQUID  or  vice  versa  to 
correct. 
Check the wiring for an open circuit.  An open circuit is 
the most common issue with a 0 mA signal. 
Check  the  installation  of  the  transmitter.    Bad 
installation  fittings  will  cause  false  signals  near  the  top 
of  the  tank,  which  typically  translates  to  a  signal 
between 19 and 20 mA.  Also look for interference just 
below the transmitter.  If the transmitter is installed in a 
metal fitting, switch to a plastic fitting. 
Immediately  check  the  wiring  for  a  short  circuit.    The 
LVU800  Series  is  current  limited  to  22  mA.    Anything 
above 23 mA indicates a short circuit. 
 
  SOLUTION 
22 
Step Seven 
 

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents