Connect DC Power to a PA-7050 Firewall

The following procedure describes how to connect power to DC power supplies in a PA-7050
firewall. The DC power supplies require -40VDC to -60VDC power input. For details on power
requirements, see
For the DC input circuit, make sure there is a 60-amp protected circuit breaker, minimum
-40VDC to -60VDC, and a double pole on the input to the DC power. The power cables
used to connect DC power are provided with the PA-7050 firewall, but not the PA-7080
firewall.
STEP 1 |
Read
Product Safety
STEP 2 |
Put the provided ESD wrist strap on your wrist ensuring that the metal contact is touching
your skin. Then aach (snap) one end of the ground cable to the wrist strap and remove the
alligator clip from the banana clip on the other end of the ESD grounding cable. Plug the
banana clip end into one of the ESD ports located on the front of the chassis before handling
ESD sensive hardware. For details on the ESD port locaon, see
STEP 3 |
Remove the two nuts and star washers from the ground studs located on the back of the
chassis on the upper le side.
PA-7000 Series Firewall Hardware Reference
front slot cards
are properly inserted and then turn on each of the four AC
Determine PA-7000 Series Firewall Power Configuraon
Warnings.
107
Requirements.
PA-7050 Front Panel
(AC).
2021 Palo Alto Networks, Inc.
©

Advertisement

Table of Contents
loading

Table of Contents