Preparing for the Installation
Install the equipment only in a temperature- and humidity-controlled indoor area that is free of airborne
materials that can conduct electricity. Too much humidity can cause a fire. Too little humidity can
produce electrical shock and fire.
Observe these additional thermal recommendations for the location where you plan to install your
equipment:
Ensure that the ventilation in the wiring closet is adequate to maintain a temperature no higher than
40°C (104°F). (Some configurations support higher operating temperatures. See Environmental
Data in "Technical Specifications" for details.)
Install a reliable air conditioning and ventilation system.
Keep the ventilation in the wiring closet running during non-business hours; otherwise, the
equipment can overheat.
Maintain a storage temperature between -40°C (-40°F) and 70°C (158°F).
When internal system temperatures exceed the thermal shutdown temperature limit (typically about
20°C higher than normal system operating temperatures), the system's power supplies are turned off
and the switch shuts down. The system remains in the OFF state until the system has sufficient time to
cool and the internal thermal sensor measures a temperature lower than the maximum specified
ambient temperature, at which time the system restarts automatically.
Alternately, you can restart the system immediately by removing and then restoring all line power to the
system.
Safeguards are built into all Extreme Networks switches and power supply units to minimize the risk of
fire.

Controlling the Humidity Level

To maximize equipment life, keep operating humidity between 50% and 70% relative humidity (non-
condensing) during typical operation.
The equipment can operate between 5% and 95% relative humidity (non-condensing) for short
intervals.

Protecting Your System from ESD (Electrostatic Discharge)

Your system must be protected from static electricity or ESD. Take the following measures to ensure
optimum system performance:
Remove materials that can cause electrostatic generation (such as synthetic resins) from the wiring
closet.
Check the appropriateness of floor mats and flooring.
Connect metal chassis, conduit, and other metals to ground using dedicated grounding lines.
Use electrostatically safe equipment.
If you are working with pluggable interface modules, wear an ESD-preventive wrist strap and
connect the metal end to a grounded equipment rack or other source of ground.
ExtremeSwitching SLX 9250 Hardware Installation Guide