38
Connect Devices
5.2.2

Counter Inputs

Only connect SELV/PELV voltages!
Only SELV/PELV voltages shall be connected to the device terminals.
Connect shielding!
Shielded cables are recommended for the counter inputs.
When using shielded cables, the shield must be routed to the grounded DIN rail
(see Section "Connections" > "Shielding").

Figure 14: Connecting example, switching contact at counter input DI1

WAGO-TO-PASS® 761
761-111 Telecontrol Module Compact, 2 AI
Manual
Version 2.0.0