2.3

Application function

CC-Link IE Field Network Basic Diagnostics

The servo amplifier supports the following CC-Link IE Field Network Basic diagnostic functions CC-Link IE Field Network
Basic diagnostics is a function that uses an engineering tool to check the status of the master station and each slave station.
This function can be used to check detailed information such as master station parameter settings and network connection
status. Refer to the GX Works2 or GX Works3 manual for details of each function.
Function
Master station status monitor
Error details
Network status monitor
Selected group communication status
monitor

IP address setting function

IP addresses are delivered from the controller to servo amplifiers via CC-Link IE Field Network Basic.
Set the IP address required for CC-Link IE Field Network Basic communication from the following items. The IP address
range is between 0.0.0.1 and 223.255.255.254. Set the IP address within the range.
[Pr. NPA01 IP address
setting]
"00000000h" (The rotary switch is
used.)
"00000001h" (Network
parameters are used.)
The initial value of the IP address is as follows.
Item
IP address
Subnet mask
Description
The number of slave stations set with the master parameters, the IP address of the master station, and the error
codes of the master station can be checked.
The error description and corrective actions for the error that occurred can be checked.
The link scan time (current, maximum, and minimum) for each group and the number of error stations/unchecked
stations can be checked.
The details of the module status and the communication status of the selected group are displayed.
If an error occurs in the module, the cause of the error and its remedies can be checked.
Rotary switches
IP address
(SW1/SW2)
00h
1st octet
2nd octet
3rd octet
4th octet
01h to FEh
1st octet
2nd octet
3rd octet
4th octet
FFh
1st octet
2nd octet
3rd octet
4th octet
Use the value of/for [Pr. NPA02 IP address].
Use the 1st to 3rd octet values of [Pr. NPA02 IP address].
The setting value of the rotary switch (SW1/SW2) is used.
Not available.
Use the value of/for [Pr. NPA02 IP address].
Initial value
192.168.3.1
255.255.255.0
2 CC-Link IE Field Network Basic
63
2.3 Application function