Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
1.1. Select the port.
1.2. Set values for Mode, IPAddress and IPMask. Mode must be set to Normal.
1.3. Check that the correct IP address is assigned to the port.
2.
Set the TCP communication parameters by navigating to: Main menu /Configuration /
Communication /Station communication /phasor measurement /PMU Configuration /
PMUCONF . The first three parameters are related to TCP communication. The default TCP
parameters setting can be used. More information regarding TCP communication is available in the
Application manual under section Short guidance for use of TCP.
3.
Set the UDP communication parameters by navigating to: Main menu /Configuration /
Communication /Station communication /phasor measurement /PMU Configuration /
PMUCONF . The first three parameters are related to TCP communication and the rest of
parameters are related to setting of six independent UDP client groups. Each UDP group has eight
parameters. More information regarding UDP communication is available in the Application manual
under section Short guidance for use of UDP. The following steps describes setting parameters for
the first UDP group:
3.1. Enable the first UDP group by setting the parameter SendDataUDP1 to Enabled.
3.2. Set the UDP client IP address by setting the parameter UDPDestAddres1 to 192.168.1.99.
3.3. The default parameter settings can be used for the rest of parameters for the first UDP group.
9.4

Setting the TCP/UDP client communication

As an example of a TCP/UDP client, the openPDC tool (PMU Connection Tester Ver. 4.2.12) from Grid
Protection Alliance is used in this section. Install PMU Connection Tester tool on a PC with Ethernet
network adaptor available. The same PC used for PCM600 can be used to install the PMU Connection
Tester tool.
66
For the purpose of the communication set-up in this section the LAN IP address of the PC is
used, where the PDC client tool is installed.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 378-UUS Rev. J
GUID-6CEE3261-D211-4051-8CA8-5840C27C560E v2
Line differential protection RED670
Commissioning manual