ABB RED670 Commissioning Manual page 74

Line differential protection
Hide thumbs Also See for RED670:
Table of Contents

Advertisement

Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
IEC140000134 V1 EN-US
1.1. Navigate to the Settings tab.
1.2. Force the IP stack to IPv4 by setting the parameter ForceIPv4 to True.
2.
Set the Connection Parameters on PMU Connection Tester for TCP communication according to
the PMU configuration.
IEC140000135 V1 EN-US
2.1. Set Host IP to the PMU IP address configured for the port in use. Here the LANAB:1
2.2. Set Port to the IED's TCP port set in the PMU under parameter C37.118TCPport (4712 is
2.3. Set the Protocol as IEEE C37.118.2-2011.
68
IPAddress (192.168.1.10) is set.
default). Alternatively, in order to make an IEEE1344 communication, the 1344TCPport
parameter setting can be used (4713 is default).
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 378-UUS Rev. J
IEC140000134-1-en.vsd
IEC140000135-1-en.vsd
Line differential protection RED670
Commissioning manual

Advertisement

Table of Contents
loading

Table of Contents