ABB RED670 Commissioning Manual page 113

Line differential protection
Hide thumbs Also See for RED670:
Table of Contents

Advertisement

1MRK 505 378-UUS Rev. J
Table 23:
Test point
1
2
3
4
5
6
Table
23
X1
ANSI09000735 V1 EN-US
Figure 26:
Line differential protection RED670
Commissioning manual
Test points for phase-to-ground loop CG (Ohm/loop)
Reach
Value
X
[X1+XN]
R
0
X
0
R
RLdFwd
R
RFltFwPG
X
0.85·[X1+XN]
R
X
0.85·[X1+XN]
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
X
RFltFwdPG·tan (LdAngle)
R
RFltFwdPG
X
-0,5·RLdFwd·tan (ArgDir)
R
0,5·RLdFwd
is used together with figure 25.
(
X
1
4
85%
ArgNegRes
6
50% RLdFwd
0.5·RFltFwdPP
Operating characteristic for phase selection function, forward direction phase-to-phase
faults
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Comments
XN=(X
When RLdFWd < RFltFwPG
When RLdFwdPG > RFltFwPG
R≈0.491·(X1+XN)+RFltFwdPG
Can be limited by RFltFwPG
Only when RLdFwd < RFltFwPG
W
/
phase
)
3
LdAngle
5
60°
2
7
ArgDir
ANSI09000735-1-en.vsd
Testing functionality by secondary injection
-X
)/3
0
1
W
(
/
phase
)
R
Section 11
107